Induction VAV terminals | NV type

Induction VAV terminals | NV type

Type NV rectangular pressure-independent VAV air volume control terminals are designed particularly for systems with high variations in heat load.

Productspecifications

  • Pressure independent control functions.
  • For spaces with high load variation.
  • Low leakage damper (optional).
  • High accurate air flow sensor (Flo-Cross type).
  • Integrated sound attenuator (very quiet).
  • Optional: reheat coil (hot water or electric).
  • Highly energy efficient.

Application

The terminals induce room air and mix it with conditioned primary air, maintaining a nearly constant air volume to the room thus providing sufficient air movement necessary to maintain occupant comfort even in extreme load variations. This specific characteristic means that cold air ‘dumping’ will not occur and that extremely low primary air temperatures can be used, without producing excessive differences between the supply and the room air temperature. The primary air is controlled by the patented airflow sensor type Flo-Cross®.

The Induction VAV terminals can be used for supply air applications in new or refurbishment projects. The terminals can optionally be supplied with a distribution plenum and a built-in hot water or electric reheat coil. Alternatively VAV terminals are ideal to be used for CO2 control. Dependent of the indoor air quality, always the correct amount of fresh air will be supplied to the room. Off course the primary air handling system need to be suitable for this.

New Induction VAV project? Use the Barcol-Air selection tool AIRSELECT for easy selection! 

How does Induction VAV work?

Ceiling Induction VAV systems have all the energy savings advantages of VAV systems with the added capability of maintaining thermal comfort at very low turn-downs. The unique design of the VAV Induction terminals allows the unit to induce room air and mix it with conditioned primary air
without using a fan. The rate of induction can be adjusted by selecting varying inlet pressures, inlet volocities, down stream pressure loss and where required by the use of a damper in the induction port.

A conventional VAV system without induction air and without the use of special VAV diffusers can only be turned down to 50/60% to prevent cold air dumping and maintain sufficient air movement and subsequently thermal comfort to the room in accordance with the strict international comfort standards (NEN, DIN, ISO, ASHRAE, etc.). Induction VAV can maintain these standards of thermal comfort at turndown ratio’s of 20%, this represents a considerable energy saving on running cost to the client.

Cooling mode
In cooling mode an Induction VAV system offers three main benefits over other VAV systems:

  • The option of using low temperature primary air (as low as 9°C) allows the designer to achieve the same cooling load but with less air/volume. This on its turn reduces ductwork sizes and associated air handling equipment, resulting in more lettable space being available to the client. It also allows for ‘Free cooling’ over a wider outside air temp. range (moderate climates only).
  • Being able to turn down to 20% without loss of thermal comfort, will reduce the demand for large air volumes and allow the variable speed AHU’s to operate at lower volumes than conventional VAV, particularly during low load and unoccupied periods.
  • At minimum air volumes other VAV systems produce ‘dead zones’ with no air movement. Induction however overcomes this problem by maintaining a near constant air volume to the room thus providing sufficient air movement necessary to maintain an optimal indoor climate.

Reheat mode
Generally, VAV systems can only turn down to 50-60% to maintain thermal comfort in cooling mode. This unfortunately dictates that reheat must occur at 50-60% of Vmax. Reheating this high amount of primary air is very energy inefficient and costly.

Reheating with Induction VAV can occur at 20% of Vmax, this is close to the minimum fresh air requirement for a room. The system also takes advantage of heat reclaim from energy sources such as light fittings etc. by pre-heating primary air with induced air, this delays the reheat coil from energizing immediately, thus reducing reheat energy cost. 

Downloads & Links

Barcol-Air Induction VAV: our green comfort solution

Flo-Cross documentation

Barcol-Air Induction VAV NV type

© 2020 | Barcol-Air B.V.
Contact us

Need advice?

Looking for the right solution, use our selection software!

Specific questions about our systems or products? Feel free to contact us, we are happy to help you!

airselecten